VGP314/ 225-515KVA Brushless Synchronous Alternator
    DIYPOWER VGP ALTERNATOR

     VGP~314 Series
  
     
225-515 KVA

      Brushless Synchronous Alternator

Rated Date 50Hz - 1500 RPM
Rating kVA/ kW cos Φ=0.8
Duty/Ambient T °  Continuous/ 40℃ Stand by/27℃
Ins. Class/ T  ° Rise H / 125 ° K H/163° K
Phase 3 Phase 3 Phase
Voltage Y 380V 400V 415V 440V 380V 400V 415V 440V
220V 230V 240V
220V 230V 240V
YY

  220V


220V

VGP314S1

KVA 225225225225265265265265
kW 180180180180212212212212

VGP314S2

KVA 250250250250275275275275
kW 200200200200275275275275

VGP314M3

KVA 275275275260302.5302.5302.5287.5
kW 220220220208242242242230
VGP314M4 KVA 300300300282.5331.3331.3331.3312.5
kW 240240240220265265265250
VGP314M5 KVA 325325325295347.5347.5347.5318.5
kW 260260260236278278278255
VGP314L6 KVA 350350350306.3372.5372.5372.5345
kW 280280280245298298298276
VGP314L7 KVA 375375375340392.5392.5392.5362.5
kW 300300300272314314314290
VGP314L8 KVA 400400400365418.8418.8418.8387.5
kW 320320320292335335335310

Rated Date60Hz - 1800 RPM
RatingkVA/ kW cos Φ=0.8
Duty/Ambient T ° Continuous/ 40℃Stand by/27℃
Ins. Class/ T  ° RiseH / 125 ° KH/163° K
Phase3 Phase3 Phase
VoltageY380V416V440V480V380V416V440V480V
220V240V 
220V240V220V
YY
208v220V240V


240V

VGP314S1

KVA230245260275270290305330
kW184196208220216232244264

VGP314S2

KVA255270285300295315327.5355
kW204216228240236252262284

VGP314M3

KVA281.3297.5312.5330305325337.5365
kW225238250264244260270292
VGP314M4KVA310325340360327.5347.5360387.5
kW248260272288262278288310
VGP314M5 KVA 340357.5372.5390357.5377.5390420
kW 272286298312286302312336
VGP314L6 KVA 362.5380400420382.5405420452.5
kW 290304320336306324336362.3
VGP314L7 KVA 390412.5432.5450415437.5452.5485
kW 312330346360332350362388
VGP314L8 KVA 417.5440460480445467.5485515
kW 334352368384356374388412
ENVIRONMENT CONDITIONS:
In the following environments, the alternator could run continuously:
1. Altitude: do not exceed 1000m.
2. Cooling air temperature: 250~313K (-15℃~40℃).
3. Relative air humidity: do not exceed 90%.
Note: If environment conditions exceed the scope mentioned-above, please feel free to contact us.
MAIN PERFORMACE DATA:
1.    The standard protection for VGP series generators is IP23;
2.  Winding are insulated to class H;
3.  Full-damping whole salient construction guarantees generator to be operated stably in any conditions, and enable it to run under 150% rated speed(2250 r/min) for 2 minutes;
4.   VGP alternator are provided with a 2/3 winding pitch as standard, can effectively eliminated the third harmonic (3rd, 9th, 15th …etc.), and are therefore perfectly suited to installations with distorting loads, and easy to operate with the other alternator in parallel;
5.  Adjusting rate of stable voltage ≤ 1%, adjusting rate of instant voltage: -15%~+20% (60&ln, COSΦ ≤ 0.4 lagging), instant voltage recovery time ≤ 1.5s;
6.  Wave aberration rate of voltage THD ≤ 3%, telephone harmony wave factor THF ≤ 2%, telephone effective factor of TIF≤ 50. 